Torre di raffreddamento a circuito chiuso, serie FBT è fornito a fonderie che comprano una fusione reale, non un pezzo isolato. Capacità, potenza, frequenza e raffreddamento seguono il metallo e la rete.
FBT closed-circuit cooling tower — factory sheet. FBI-175-II and FBI-200-II are printed on the same sheet.| Model | Water 37–32°C (m³/h) | Water 40–32°C (m³/h) | Water 55–35°C (m³/h) | Fan power (kW) | Air flow (m³/s) | Spray pump (kW) | Spray water (m³/h) | Inlet/outlet | Working pressure (MPa) | Weight (kg) | Size L×W×H (mm) |
|---|
| FBT-100 | 100 | 65 | 45 | 1.1 | 33 | 0.75 | 22 | 80×4 | 0.35 | 3250 | 2410×3000×4620 |
| FBT-125 | 125 | 81 | 56 | 2.2 | 42 | 1.5 | 26 | 80×4 | 0.35 | 3545 | 2410×5220×4620 |
| FBT-150 | 150 | 95 | 67 | 3 | 42 | 1.5 | 26 | 80×4 | 0.35 | 3785 | 2410×5220×4620 |
| FBT-175 | 175 | 109 | 78 | 3 | 50 | 1.5 | 44 | 80×8 | 0.35 | 4300 | 2410×3000×4620 |
| FBT-200 | 200 | 130 | 90 | 4.4 | 63 | 2.2 | 44 | 80×8 | 0.35 | 4750 | 2410×3550×4620 |
| FBT-250 | 250 | 162 | 112 | 4.4 | 56 | 2.2 | 52 | 80×8 | 0.5 | 5300 | 2410×3550×4620 |
| FBT-300 | 300 | 190 | 132 | 4.4 | 82 | 2.2 | 52 | 100×12 | 0.5 | 6200 | 2410×3550×4620 |
| FBT-350 | 350 | 221 | 154 | 6 | 82 | 3 | 88 | 100×12 | 0.5 | 7000 | 2410×3550×4620 |
| FBT-400 | 400 | 260 | 180 | 6 | 126 | 4 | 88 | 100×8 | 0.6 | 8100 | 2410×2510×4620 |
| FBT-450 | 450 | 291 | 200 | 8 | 126 | 5.5 | 132 | 100×8 | 0.6 | 8700 | 2410×2510×4620 |
| FBT-500 | 500 | 320 | 227 | 12 | 126 | 5.5 | 132 | 100×8 | 0.6 | 9350 | 2140×2510×4620 |
| FBT-60-II | 60 | 39 | 27 | 12 | 25 | 7.5 | 22 | 80×4 | 0.3 | 2800 | 2410×2510×4620 |
| FBT-70-II | 70 | 45 | 31 | 16 | 25 | 4×2 | 22 | 80×4 | 0.35 | 2950 | 2410×2510×4620 |
| FBT-80-II | 80 | 52 | 36 | 16 | 33 | 5.5×2 | 26 | 100×4 | 0.35 | 3250 | 2410×2510×4620 |
| FBT-100-II | 100 | 55 | 45 | 24 | 33 | 5.5×2 | 26 | 100×4 | 0.35 | 3420 | 2410×2510×4620 |
| FBT-125-II | 125 | 81 | 58 | 24 | 42 | 7.5×2 | 26 | 100×4 | 0.35 | 3780 | 2410×2510×4620 |
| FBT-150-II | 150 | 96 | 67 | 24 | 42 | 4×4 | 44 | 80×8 | 0.35 | 4150 | 2410×2510×4620 |
| FBI-175-II | 175 | 109 | 78 | 32 | 48 | 4×4 | 44 | 80×8 | 0.4 | 4350 | 2410×2910×4620 |
| FBI-200-II | 200 | 130 | 90 | 32 | 48 | 5.5×4 | 44 | 80×8 | 0.5 | 4950 | 2410×2910×4620 |
FBT series points — factory sheet| Item | Catalog statement |
|---|
| Process water | Soft water in a closed coil, no contact with outside air, no scaling in the furnace circuit |
| Open pond | Not used on the process-water side |
| Spray section | Collects spray water; the coil stays clean |
| Fan drive | Low-power motor with a gear reducer |
| Cold climate | Antifreeze heating, cooling and heating in one tower |
| Energy statement on the sheet | About 30% less than comparable domestic towers, small fan and high water flow |
American standards| US standard | Applies to |
|---|
| CTI STD-201 | Cooling Technology Institute thermal performance for US towers |
| NEMA MG 1 | Fan and pump motors |
| NFPA 70 (NEC) | Tower and pump electrical supply |
Every figure in these tables is taken from the factory sheets in the product folder and is written in English. 1 metric ton = 1.102 US short tons. Power-supply ratings can still be negotiated to the customer requirement, as the sheet itself states. American standards are the US specifications normally requested with this equipment.
Torre di raffreddamento a flusso incrociato, serie HL è fornito a fonderie che comprano una fusione reale, non un pezzo isolato. Capacità, potenza, frequenza e raffreddamento seguono il metallo e la rete.
HL crossflow cooling tower — factory sheet. A fan or pump entry such as 5.5×2 means two units.| Model | Water 37–32°C (m³/h) | Water 40–32°C (m³/h) | Water 55–35°C (m³/h) | Fan power (kW) | Air flow (m³/s) | Spray pump (kW) | Spray water (m³/h) | Inlet/outlet | Working pressure (MPa) | Weight (kg) | Size L×W×H (mm) |
|---|
| HL-20 | 20 | 13 | 9 | 4×2 | 4.5 | 3.7 | 5.5 | 65×2 | 0.25 | 750 | 2050×1280×2000 |
| HL-30 | 30 | 19 | 13 | 5.5×2 | 7 | 2.2×2 | 8 | 80×2 | 0.25 | 1050 | 2510×1280×2100 |
| HL-40 | 40 | 26 | 18 | 5.5×2 | 7 | 2.2×2 | 10 | 80×2 | 0.3 | 1150 | 2510×1280×2200 |
| HL-50 | 50 | 33 | 23 | 4×3 | 11 | 3.7×2 | 13 | 80×2 | 0.3 | 1300 | 2510×1280×2550 |
| HL-60 | 60 | 39 | 27 | 5.5×3 | 13 | 2.2×4 | 15 | 100×2 | 0.3 | 1450 | 2510×1530×2650 |
| HL-70 | 70 | 45 | 31 | 4×4 | 15 | 2.2×4 | 17 | 100×2 | 0.35 | 1850 | 2510×1530×2750 |
| HL-80 | 80 | 52 | 36 | 5.5×4 | 17 | 3.7×4 | 20 | 100×2 | 0.35 | 2050 | 2510×1530×2850 |
| HL-100 | 100 | 65 | 45 | 5.5×4 | 25 | 3.7×4 | 30 | 80×4 | 0.35 | 2850 | 3000×1780×2850 |
| HL-125 | 125 | 81 | 56 | 5.5×6 | 30 | 3.7×6 | 40 | 100×4 | 0.35 | 3250 | 3000×1780×2950 |
| HL-150 | 150 | 95 | 67 | 5.5×6 | 40 | 3.7×6 | 50 | 80×8 | 0.35 | 3750 | 3000×2130×3350 |
| HL-175 | 175 | 109 | 78 | 5.5×6 | 45 | 3.7 | 50 | 80×8 | 0.35 | 4095 | 3940×2210×3450 |
| HL-200 | 200 | 130 | 90 | 3×2 | 50 | 3.7 | 60 | 80×8 | 0.35 | 4500 | 3940×2210×3550 |
| HL-250 | 250 | 162 | 112 | 3×2 | 60 | 2.2×2 | 80 | 100×8 | 0.5 | 6120 | 4300×2500×3350 |
| HL-300 | 300 | 190 | 132 | 4×2 | 80 | 2.2×2 | 100 | 80×16 | 0.5 | 6840 | 3000×5000×3350 |
| HL-350 | 350 | 221 | 154 | 4×2 | 100 | 2.2×2 | 100 | 80×16 | 0.5 | 7600 | 3940×5200×3450 |
| HL-400 | 400 | 260 | 180 | 5.5×2 | 120 | 3.7×2 | 120 | 80×16 | 0.6 | 8500 | 3940×5200×3550 |
| HL-450 | 450 | 291 | 200 | 5.5×2 | 120 | 3.7×2 | 120 | 100×16 | 0.6 | 9450 | 4300×5200×3550 |
| HL-500 | 500 | 320 | 227 | 7.5×2 | 120 | 3.7×2 | 120 | 100×16 | 0.6 | 9900 | 4300×5700×3550 |
| HL-550 | 550 | 350 | 250 | 7.5×2 | 130 | 3.7×2 | 130 | 100×16 | 0.6 | 11500 | 4300×5700×3750 |
HL series points — factory sheet| Item | Catalog statement |
|---|
| Winter | Fan can stay off; cooling is by gravity flow |
| Drift loss | About 0.5%, with a drift eliminator |
| Water make-up | About 1% |
| Basin | Built onto the tower, so a separate cold-water pit is not required |
| Wear parts | Make-up water, fan and motor |
American standards| US standard | Applies to |
|---|
| CTI STD-201 | Cooling Technology Institute thermal performance for US towers |
| NEMA MG 1 | Fan and pump motors |
| NFPA 70 (NEC) | Tower and pump electrical supply |
Every figure in these tables is taken from the factory sheets in the product folder and is written in English. 1 metric ton = 1.102 US short tons. Power-supply ratings can still be negotiated to the customer requirement, as the sheet itself states. American standards are the US specifications normally requested with this equipment.
Raffreddamento ad acqua di bobina, alimentazione e condensatori è fornito a fonderie che comprano una fusione reale, non un pezzo isolato. Capacità, potenza, frequenza e raffreddamento seguono il metallo e la rete.
FBT closed-circuit cooling tower — factory sheet. FBI-175-II and FBI-200-II are printed on the same sheet.| Model | Water 37–32°C (m³/h) | Water 40–32°C (m³/h) | Water 55–35°C (m³/h) | Fan power (kW) | Air flow (m³/s) | Spray pump (kW) | Spray water (m³/h) | Inlet/outlet | Working pressure (MPa) | Weight (kg) | Size L×W×H (mm) |
|---|
| FBT-100 | 100 | 65 | 45 | 1.1 | 33 | 0.75 | 22 | 80×4 | 0.35 | 3250 | 2410×3000×4620 |
| FBT-125 | 125 | 81 | 56 | 2.2 | 42 | 1.5 | 26 | 80×4 | 0.35 | 3545 | 2410×5220×4620 |
| FBT-150 | 150 | 95 | 67 | 3 | 42 | 1.5 | 26 | 80×4 | 0.35 | 3785 | 2410×5220×4620 |
| FBT-175 | 175 | 109 | 78 | 3 | 50 | 1.5 | 44 | 80×8 | 0.35 | 4300 | 2410×3000×4620 |
| FBT-200 | 200 | 130 | 90 | 4.4 | 63 | 2.2 | 44 | 80×8 | 0.35 | 4750 | 2410×3550×4620 |
| FBT-250 | 250 | 162 | 112 | 4.4 | 56 | 2.2 | 52 | 80×8 | 0.5 | 5300 | 2410×3550×4620 |
| FBT-300 | 300 | 190 | 132 | 4.4 | 82 | 2.2 | 52 | 100×12 | 0.5 | 6200 | 2410×3550×4620 |
| FBT-350 | 350 | 221 | 154 | 6 | 82 | 3 | 88 | 100×12 | 0.5 | 7000 | 2410×3550×4620 |
| FBT-400 | 400 | 260 | 180 | 6 | 126 | 4 | 88 | 100×8 | 0.6 | 8100 | 2410×2510×4620 |
| FBT-450 | 450 | 291 | 200 | 8 | 126 | 5.5 | 132 | 100×8 | 0.6 | 8700 | 2410×2510×4620 |
| FBT-500 | 500 | 320 | 227 | 12 | 126 | 5.5 | 132 | 100×8 | 0.6 | 9350 | 2140×2510×4620 |
| FBT-60-II | 60 | 39 | 27 | 12 | 25 | 7.5 | 22 | 80×4 | 0.3 | 2800 | 2410×2510×4620 |
| FBT-70-II | 70 | 45 | 31 | 16 | 25 | 4×2 | 22 | 80×4 | 0.35 | 2950 | 2410×2510×4620 |
| FBT-80-II | 80 | 52 | 36 | 16 | 33 | 5.5×2 | 26 | 100×4 | 0.35 | 3250 | 2410×2510×4620 |
| FBT-100-II | 100 | 55 | 45 | 24 | 33 | 5.5×2 | 26 | 100×4 | 0.35 | 3420 | 2410×2510×4620 |
| FBT-125-II | 125 | 81 | 58 | 24 | 42 | 7.5×2 | 26 | 100×4 | 0.35 | 3780 | 2410×2510×4620 |
| FBT-150-II | 150 | 96 | 67 | 24 | 42 | 4×4 | 44 | 80×8 | 0.35 | 4150 | 2410×2510×4620 |
| FBI-175-II | 175 | 109 | 78 | 32 | 48 | 4×4 | 44 | 80×8 | 0.4 | 4350 | 2410×2910×4620 |
| FBI-200-II | 200 | 130 | 90 | 32 | 48 | 5.5×4 | 44 | 80×8 | 0.5 | 4950 | 2410×2910×4620 |
FBT series points — factory sheet| Item | Catalog statement |
|---|
| Process water | Soft water in a closed coil, no contact with outside air, no scaling in the furnace circuit |
| Open pond | Not used on the process-water side |
| Spray section | Collects spray water; the coil stays clean |
| Fan drive | Low-power motor with a gear reducer |
| Cold climate | Antifreeze heating, cooling and heating in one tower |
| Energy statement on the sheet | About 30% less than comparable domestic towers, small fan and high water flow |
American standards| US standard | Applies to |
|---|
| CTI STD-201 | Cooling Technology Institute thermal performance for US towers |
| NEMA MG 1 | Fan and pump motors |
| NFPA 70 (NEC) | Tower and pump electrical supply |
Every figure in these tables is taken from the factory sheets in the product folder and is written in English. 1 metric ton = 1.102 US short tons. Power-supply ratings can still be negotiated to the customer requirement, as the sheet itself states. American standards are the US specifications normally requested with this equipment.
HL crossflow cooling tower — factory sheet. A fan or pump entry such as 5.5×2 means two units.| Model | Water 37–32°C (m³/h) | Water 40–32°C (m³/h) | Water 55–35°C (m³/h) | Fan power (kW) | Air flow (m³/s) | Spray pump (kW) | Spray water (m³/h) | Inlet/outlet | Working pressure (MPa) | Weight (kg) | Size L×W×H (mm) |
|---|
| HL-20 | 20 | 13 | 9 | 4×2 | 4.5 | 3.7 | 5.5 | 65×2 | 0.25 | 750 | 2050×1280×2000 |
| HL-30 | 30 | 19 | 13 | 5.5×2 | 7 | 2.2×2 | 8 | 80×2 | 0.25 | 1050 | 2510×1280×2100 |
| HL-40 | 40 | 26 | 18 | 5.5×2 | 7 | 2.2×2 | 10 | 80×2 | 0.3 | 1150 | 2510×1280×2200 |
| HL-50 | 50 | 33 | 23 | 4×3 | 11 | 3.7×2 | 13 | 80×2 | 0.3 | 1300 | 2510×1280×2550 |
| HL-60 | 60 | 39 | 27 | 5.5×3 | 13 | 2.2×4 | 15 | 100×2 | 0.3 | 1450 | 2510×1530×2650 |
| HL-70 | 70 | 45 | 31 | 4×4 | 15 | 2.2×4 | 17 | 100×2 | 0.35 | 1850 | 2510×1530×2750 |
| HL-80 | 80 | 52 | 36 | 5.5×4 | 17 | 3.7×4 | 20 | 100×2 | 0.35 | 2050 | 2510×1530×2850 |
| HL-100 | 100 | 65 | 45 | 5.5×4 | 25 | 3.7×4 | 30 | 80×4 | 0.35 | 2850 | 3000×1780×2850 |
| HL-125 | 125 | 81 | 56 | 5.5×6 | 30 | 3.7×6 | 40 | 100×4 | 0.35 | 3250 | 3000×1780×2950 |
| HL-150 | 150 | 95 | 67 | 5.5×6 | 40 | 3.7×6 | 50 | 80×8 | 0.35 | 3750 | 3000×2130×3350 |
| HL-175 | 175 | 109 | 78 | 5.5×6 | 45 | 3.7 | 50 | 80×8 | 0.35 | 4095 | 3940×2210×3450 |
| HL-200 | 200 | 130 | 90 | 3×2 | 50 | 3.7 | 60 | 80×8 | 0.35 | 4500 | 3940×2210×3550 |
| HL-250 | 250 | 162 | 112 | 3×2 | 60 | 2.2×2 | 80 | 100×8 | 0.5 | 6120 | 4300×2500×3350 |
| HL-300 | 300 | 190 | 132 | 4×2 | 80 | 2.2×2 | 100 | 80×16 | 0.5 | 6840 | 3000×5000×3350 |
| HL-350 | 350 | 221 | 154 | 4×2 | 100 | 2.2×2 | 100 | 80×16 | 0.5 | 7600 | 3940×5200×3450 |
| HL-400 | 400 | 260 | 180 | 5.5×2 | 120 | 3.7×2 | 120 | 80×16 | 0.6 | 8500 | 3940×5200×3550 |
| HL-450 | 450 | 291 | 200 | 5.5×2 | 120 | 3.7×2 | 120 | 100×16 | 0.6 | 9450 | 4300×5200×3550 |
| HL-500 | 500 | 320 | 227 | 7.5×2 | 120 | 3.7×2 | 120 | 100×16 | 0.6 | 9900 | 4300×5700×3550 |
| HL-550 | 550 | 350 | 250 | 7.5×2 | 130 | 3.7×2 | 130 | 100×16 | 0.6 | 11500 | 4300×5700×3750 |
HL series points — factory sheet| Item | Catalog statement |
|---|
| Winter | Fan can stay off; cooling is by gravity flow |
| Drift loss | About 0.5%, with a drift eliminator |
| Water make-up | About 1% |
| Basin | Built onto the tower, so a separate cold-water pit is not required |
| Wear parts | Make-up water, fan and motor |
American standards| US standard | Applies to |
|---|
| CTI STD-201 | Cooling Technology Institute thermal performance for US towers |
| NEMA MG 1 | Fan and pump motors |
| NFPA 70 (NEC) | Tower and pump electrical supply |
Every figure in these tables is taken from the factory sheets in the product folder and is written in English. 1 metric ton = 1.102 US short tons. Power-supply ratings can still be negotiated to the customer requirement, as the sheet itself states. American standards are the US specifications normally requested with this equipment.
Stazione di raffreddamento per sistemi di forno a induzione è fornito a fonderie che comprano una fusione reale, non un pezzo isolato. Capacità, potenza, frequenza e raffreddamento seguono il metallo e la rete.
FBT closed-circuit cooling tower — factory sheet. FBI-175-II and FBI-200-II are printed on the same sheet.| Model | Water 37–32°C (m³/h) | Water 40–32°C (m³/h) | Water 55–35°C (m³/h) | Fan power (kW) | Air flow (m³/s) | Spray pump (kW) | Spray water (m³/h) | Inlet/outlet | Working pressure (MPa) | Weight (kg) | Size L×W×H (mm) |
|---|
| FBT-100 | 100 | 65 | 45 | 1.1 | 33 | 0.75 | 22 | 80×4 | 0.35 | 3250 | 2410×3000×4620 |
| FBT-125 | 125 | 81 | 56 | 2.2 | 42 | 1.5 | 26 | 80×4 | 0.35 | 3545 | 2410×5220×4620 |
| FBT-150 | 150 | 95 | 67 | 3 | 42 | 1.5 | 26 | 80×4 | 0.35 | 3785 | 2410×5220×4620 |
| FBT-175 | 175 | 109 | 78 | 3 | 50 | 1.5 | 44 | 80×8 | 0.35 | 4300 | 2410×3000×4620 |
| FBT-200 | 200 | 130 | 90 | 4.4 | 63 | 2.2 | 44 | 80×8 | 0.35 | 4750 | 2410×3550×4620 |
| FBT-250 | 250 | 162 | 112 | 4.4 | 56 | 2.2 | 52 | 80×8 | 0.5 | 5300 | 2410×3550×4620 |
| FBT-300 | 300 | 190 | 132 | 4.4 | 82 | 2.2 | 52 | 100×12 | 0.5 | 6200 | 2410×3550×4620 |
| FBT-350 | 350 | 221 | 154 | 6 | 82 | 3 | 88 | 100×12 | 0.5 | 7000 | 2410×3550×4620 |
| FBT-400 | 400 | 260 | 180 | 6 | 126 | 4 | 88 | 100×8 | 0.6 | 8100 | 2410×2510×4620 |
| FBT-450 | 450 | 291 | 200 | 8 | 126 | 5.5 | 132 | 100×8 | 0.6 | 8700 | 2410×2510×4620 |
| FBT-500 | 500 | 320 | 227 | 12 | 126 | 5.5 | 132 | 100×8 | 0.6 | 9350 | 2140×2510×4620 |
| FBT-60-II | 60 | 39 | 27 | 12 | 25 | 7.5 | 22 | 80×4 | 0.3 | 2800 | 2410×2510×4620 |
| FBT-70-II | 70 | 45 | 31 | 16 | 25 | 4×2 | 22 | 80×4 | 0.35 | 2950 | 2410×2510×4620 |
| FBT-80-II | 80 | 52 | 36 | 16 | 33 | 5.5×2 | 26 | 100×4 | 0.35 | 3250 | 2410×2510×4620 |
| FBT-100-II | 100 | 55 | 45 | 24 | 33 | 5.5×2 | 26 | 100×4 | 0.35 | 3420 | 2410×2510×4620 |
| FBT-125-II | 125 | 81 | 58 | 24 | 42 | 7.5×2 | 26 | 100×4 | 0.35 | 3780 | 2410×2510×4620 |
| FBT-150-II | 150 | 96 | 67 | 24 | 42 | 4×4 | 44 | 80×8 | 0.35 | 4150 | 2410×2510×4620 |
| FBI-175-II | 175 | 109 | 78 | 32 | 48 | 4×4 | 44 | 80×8 | 0.4 | 4350 | 2410×2910×4620 |
| FBI-200-II | 200 | 130 | 90 | 32 | 48 | 5.5×4 | 44 | 80×8 | 0.5 | 4950 | 2410×2910×4620 |
FBT series points — factory sheet| Item | Catalog statement |
|---|
| Process water | Soft water in a closed coil, no contact with outside air, no scaling in the furnace circuit |
| Open pond | Not used on the process-water side |
| Spray section | Collects spray water; the coil stays clean |
| Fan drive | Low-power motor with a gear reducer |
| Cold climate | Antifreeze heating, cooling and heating in one tower |
| Energy statement on the sheet | About 30% less than comparable domestic towers, small fan and high water flow |
American standards| US standard | Applies to |
|---|
| CTI STD-201 | Cooling Technology Institute thermal performance for US towers |
| NEMA MG 1 | Fan and pump motors |
| NFPA 70 (NEC) | Tower and pump electrical supply |
Every figure in these tables is taken from the factory sheets in the product folder and is written in English. 1 metric ton = 1.102 US short tons. Power-supply ratings can still be negotiated to the customer requirement, as the sheet itself states. American standards are the US specifications normally requested with this equipment.
HL crossflow cooling tower — factory sheet. A fan or pump entry such as 5.5×2 means two units.| Model | Water 37–32°C (m³/h) | Water 40–32°C (m³/h) | Water 55–35°C (m³/h) | Fan power (kW) | Air flow (m³/s) | Spray pump (kW) | Spray water (m³/h) | Inlet/outlet | Working pressure (MPa) | Weight (kg) | Size L×W×H (mm) |
|---|
| HL-20 | 20 | 13 | 9 | 4×2 | 4.5 | 3.7 | 5.5 | 65×2 | 0.25 | 750 | 2050×1280×2000 |
| HL-30 | 30 | 19 | 13 | 5.5×2 | 7 | 2.2×2 | 8 | 80×2 | 0.25 | 1050 | 2510×1280×2100 |
| HL-40 | 40 | 26 | 18 | 5.5×2 | 7 | 2.2×2 | 10 | 80×2 | 0.3 | 1150 | 2510×1280×2200 |
| HL-50 | 50 | 33 | 23 | 4×3 | 11 | 3.7×2 | 13 | 80×2 | 0.3 | 1300 | 2510×1280×2550 |
| HL-60 | 60 | 39 | 27 | 5.5×3 | 13 | 2.2×4 | 15 | 100×2 | 0.3 | 1450 | 2510×1530×2650 |
| HL-70 | 70 | 45 | 31 | 4×4 | 15 | 2.2×4 | 17 | 100×2 | 0.35 | 1850 | 2510×1530×2750 |
| HL-80 | 80 | 52 | 36 | 5.5×4 | 17 | 3.7×4 | 20 | 100×2 | 0.35 | 2050 | 2510×1530×2850 |
| HL-100 | 100 | 65 | 45 | 5.5×4 | 25 | 3.7×4 | 30 | 80×4 | 0.35 | 2850 | 3000×1780×2850 |
| HL-125 | 125 | 81 | 56 | 5.5×6 | 30 | 3.7×6 | 40 | 100×4 | 0.35 | 3250 | 3000×1780×2950 |
| HL-150 | 150 | 95 | 67 | 5.5×6 | 40 | 3.7×6 | 50 | 80×8 | 0.35 | 3750 | 3000×2130×3350 |
| HL-175 | 175 | 109 | 78 | 5.5×6 | 45 | 3.7 | 50 | 80×8 | 0.35 | 4095 | 3940×2210×3450 |
| HL-200 | 200 | 130 | 90 | 3×2 | 50 | 3.7 | 60 | 80×8 | 0.35 | 4500 | 3940×2210×3550 |
| HL-250 | 250 | 162 | 112 | 3×2 | 60 | 2.2×2 | 80 | 100×8 | 0.5 | 6120 | 4300×2500×3350 |
| HL-300 | 300 | 190 | 132 | 4×2 | 80 | 2.2×2 | 100 | 80×16 | 0.5 | 6840 | 3000×5000×3350 |
| HL-350 | 350 | 221 | 154 | 4×2 | 100 | 2.2×2 | 100 | 80×16 | 0.5 | 7600 | 3940×5200×3450 |
| HL-400 | 400 | 260 | 180 | 5.5×2 | 120 | 3.7×2 | 120 | 80×16 | 0.6 | 8500 | 3940×5200×3550 |
| HL-450 | 450 | 291 | 200 | 5.5×2 | 120 | 3.7×2 | 120 | 100×16 | 0.6 | 9450 | 4300×5200×3550 |
| HL-500 | 500 | 320 | 227 | 7.5×2 | 120 | 3.7×2 | 120 | 100×16 | 0.6 | 9900 | 4300×5700×3550 |
| HL-550 | 550 | 350 | 250 | 7.5×2 | 130 | 3.7×2 | 130 | 100×16 | 0.6 | 11500 | 4300×5700×3750 |
HL series points — factory sheet| Item | Catalog statement |
|---|
| Winter | Fan can stay off; cooling is by gravity flow |
| Drift loss | About 0.5%, with a drift eliminator |
| Water make-up | About 1% |
| Basin | Built onto the tower, so a separate cold-water pit is not required |
| Wear parts | Make-up water, fan and motor |
American standards| US standard | Applies to |
|---|
| CTI STD-201 | Cooling Technology Institute thermal performance for US towers |
| NEMA MG 1 | Fan and pump motors |
| NFPA 70 (NEC) | Tower and pump electrical supply |
Every figure in these tables is taken from the factory sheets in the product folder and is written in English. 1 metric ton = 1.102 US short tons. Power-supply ratings can still be negotiated to the customer requirement, as the sheet itself states. American standards are the US specifications normally requested with this equipment.